Chapter 6: Operation
The reset time must be set high enough to allow all enabled escalation levels to be notified about an
alarm before it is reset.
Sample Alarm Message – (E-mail format):
From:
Sensaphone WEB600
ACME Widgets Monitoring System
Oak & Pine St - Hatfield, PA
High Alarm detected on Zone 1: Server Room Temp
Alarm occurred on Sunday, February 8, 2009 at 9:18:27pm
It is now 87.1F
Level crossed limit of 85.0F
RETURN-TO-NORMAL ALARM MESSAGES
If a zone is programmed with the Return-to-Normal option enabled, then a message will be sent to
those profiles/Contacts that were sent the original alarm message, informing them that the condition
has gone back to a normal condition. Those Profiles/Contacts that did not receive the original alarm
message due to Scheduling, Escalation or Network Service Disruption will not receive the Return-to-
Normal message.
NETWORK SERVICE DISRUPTION
In the event that the Ethernet network (or e-mail server) becomes unavailable due to a service disrup-
tion or power failure, the WEB600 will hold the current alarm messages until service is restored, how-
ever, if both power and battery fail or the alarm no longer exists before the network services are restored
then the alarm messages will be lost.